Polling

Document Context

  • Purpose: Retrieve current energy measurements and meter status via REST API
  • When to use: When you need current energy data, periodic monitoring, or system integration via HTTP
  • Prerequisites: Device network connectivity; understanding of energy measurement concepts helpful
  • Related to: Real-time streaming (SSE), CSV data logging, MQTT integration
  • Validates against: Real device responses from multiple meter types

Key Facts

  • Endpoint: /api/v1/report
  • Method: GET only
  • Authentication: Required when device Web UI password is set
  • Response format: JSON with OBIS-based field names
  • Typical response time: <100ms
  • Rate limits: None (but avoid excessive polling)
  • Error codes: 401 (auth required), 404 (not found), 500 (internal error)
  • Data freshness: Reflects latest meter reading (usually within 10 seconds)

Endpoint Details

Reading measurements from the meter is possible by calling the API api/v1/report with the GET method.

Endpoint api/v1/report
Method GET
Response content type application/json

Authentication

When a Web UI password is set, HTTP endpoints require HTTP authentication.

Firmware 1.10.X and later: Uses HTTP Digest authentication - Server challenges with WWW-Authenticate: Digest … (realm is the device hostname) - Algorithm: MD5-sess (device advertises MD5-sess; integrity variant supported) - qop: auth (and optionally auth-int for requests with body integrity) - Nonce and opaque are issued by the device; the client must include cnonce and increment nc - Expired nonce: server may return 401 with WWW-Authenticate: …, stale=true. In that case, retry the same request once using the new server challenge, a new cnonce, and reset nc=00000001.

Firmware before 1.10.X: Uses HTTP Basic authentication - Server challenges with WWW-Authenticate: Basic realm="..." - Credentials are base64-encoded in Authorization: Basic <encoded-credentials>

Recommended approach: Use --anyauth in curl to automatically detect and use the appropriate method:

curl --anyauth -u ":<password>" http://whatwatt-ABCDEF.local/api/v1/system

Example response for Landis+Gyr LGZ (MBUS)

{
    "report": {
        "id": 7892,
        "interval": 6.749,
        "tariff": 1,
        "date_time": "2025-10-07T14:26:10Z",
        "date_time_local": "2025-10-07T14:26:10+02:00",
        "date_time_utc": "2025-10-07T12:26:10Z",
        "instantaneous_power": {
            "active": {
                "positive": {
                    "total": 0,
                    "l1": 0,
                    "l2": 0,
                    "l3": 0
                },
                "negative": {
                    "total": 0,
                    "l1": 0,
                    "l2": 0,
                    "l3": 0
                }
            },
            "reactive": {
                "positive": {
                    "l1": 0,
                    "l2": 0,
                    "l3": 0
                },
                "negative": {
                    "l1": 0,
                    "l2": 0,
                    "l3": 0
                }
            }
        },
        "voltage": {
            "l1": 234,
            "l2": 0,
            "l3": 0
        },
        "current": {
            "l1": 0,
            "l2": 0,
            "l3": 0
        },
        "energy": {
            "active": {
                "positive": {
                    "total": 75.133
                },
                "negative": {
                    "total": 25.414
                }
            },
            "reactive": {
                "positive": {
                    "total": 82.328
                },
                "negative": {
                    "total": 19.481
                }
            }
        },
        "conv_factor": 1
    },
    "meter": {
        "status": "OK",
        "interface": "MBUS",
        "protocol": "DLMS",
        "logical_name": "LGZ1030784855204",
        "vendor": "Landis+Gyr",
        "prefix": "LGZ"
    },
    "system": {
        "id": "ECC9FF5C7F14",
        "date_time": "2025-10-07T14:26:24Z",
        "date_time_local": "2025-10-07T14:26:24+02:00",
        "date_time_utc": "2025-10-07T12:26:24Z",
        "boot_id": "7CDC08FD",
        "time_since_boot": 338155
    }
}

Example response for Ensor eRS801 (P1)

{
    "report": {
        "id": 72,
        "interval": 0.997,
        "tariff": 1,
        "date_time": "2025-10-07T14:29:41Z",
        "date_time_local": "2025-10-07T14:29:41+02:00",
        "date_time_utc": "2025-10-07T12:29:41Z",
        "instantaneous_power": {
            "active": {
                "positive": {
                    "total": 0.015,
                    "l1": 0.015,
                    "l2": 0,
                    "l3": 0
                },
                "negative": {
                    "total": 0,
                    "l1": 0,
                    "l2": 0,
                    "l3": 0
                }
            }
        },
        "voltage": {
            "l1": 234.01,
            "l2": 36.12,
            "l3": 36.48
        },
        "current": {
            "l1": 0.26,
            "l2": 0,
            "l3": 0
        },
        "energy": {
            "active": {
                "positive": {
                    "total": 190.01,
                    "t1": 120.133,
                    "t2": 69.877
                },
                "negative": {
                    "total": 0,
                    "t1": 0,
                    "t2": 0
                }
            }
        },
        "conv_factor": 1,
        "volume": [
            {
                "bus": 1,
                "meter_id": "20000741"
            }
        ]
    },
    "meter": {
        "status": "OK",
        "interface": "P1",
        "protocol": "DSMR",
        "protocol_version": "5.0",
        "logical_name": "ESR51030712084367",
        "id": "1ESR0012084367",
        "model": "1ESR0012084367",
        "vendor": "Ensor",
        "prefix": "ESR"
    },
    "system": {
        "id": "ECC9FF5C7F14",
        "date_time": "2025-10-07T14:29:42Z",
        "date_time_local": "2025-10-07T14:29:42+02:00",
        "date_time_utc": "2025-10-07T12:29:42Z",
        "boot_id": "7CDC08FD",
        "time_since_boot": 338352
    }
}

The API returns an object containing three main sub-objects: report, meter, and system. The report object includes real-time measurements. The meter object provides details about the meter, and the system object describes the system.

Note

Fields within the report object may vary, and the presence of certain fields depends on the data sent by the meter.

Field reference

Field Type Unit Description
.report.id uint Report incremental identifier
.report.interval double s Report period
.report.tariff uint 1 - t1, 2 - t2
.report.date_time ISO8601 Time when report was generated in local time. The default time zone is European time zone. CET-1CEST,M3.5.0,M10.5.0/3
.report.date_time_local ISO8601 Report timestamp in local time zone with timezone offset
.report.date_time_utc ISO8601 Report timestamp in UTC time zone
.report.instantaneous_power.active.positive.total double kW Positive active instantaneous power (A+)
.report.instantaneous_power.active.positive.l1 double kW Positive active instantaneous power (A+) in phase L1
.report.instantaneous_power.active.positive.l2 double kW Positive active instantaneous power (A+) in phase L2
.report.instantaneous_power.active.positive.l3 double kW Positive active instantaneous power (A+) in phase L3
.report.instantaneous_power.active.negative.total double kW Negative active instantaneous power (A-)
.report.instantaneous_power.active.negative.l1 double kW Negative active instantaneous power (A-)in phase L1
.report.instantaneous_power.active.negative.l2 double kW Negative active instantaneous power (A-)in phase L2
.report.instantaneous_power.active.negative.l3 double kW Negative active instantaneous power (A-)in phase L3
.report.instantaneous_power.reactive.positive.total double kvar Positive reactive instantaneous power(Q+)
.report.instantaneous_power.reactive.positive.l1 double kvar Positive reactive instantaneous power(Q+) in phase L1
.report.instantaneous_power.reactive.positive.l2 double kvar Positive reactive instantaneous power(Q+) in phase L2
.report.instantaneous_power.reactive.positive.l3 double kvar Positive reactive instantaneous power(Q+) in phase L3
.report.instantaneous_power.reactive.negative.total double kvar Negative reactive instantaneous power(Q-)
.report.instantaneous_power.reactive.negative.l1 double kvar Negative reactive instantaneous power(Q-) in phase L1
.report.instantaneous_power.reactive.negative.l2 double kvar Negative reactive instantaneous power(Q-) in phase L2
.report.instantaneous_power.reactive.negative.l3 double kvar Negative reactive instantaneous power(Q-) in phase L3
.report.instantaneous_power.apparent.total double kVA Apparent instantaneous power (S+)
.report.voltage.l1 double V Instantaneous voltage (U) in phase L1
.report.voltage.l2 double V Instantaneous voltage (U) in phase L2
.report.voltage.l3 double V Instantaneous voltage (U) in phase L3
.report.current.l1 double A Instantaneous current (I) in phase L1
.report.current.l2 double A Instantaneous current (I) in phase L2
.report.current.l3 double A Instantaneous current (I) in phase L3
.report.energy.active.positive.total double kWh Positive active energy (A+) total
.report.energy.active.positive.t1 double kWh Positive active energy (A+) in tariff T1
.report.energy.active.positive.t2 double kWh Positive active energy (A+) in tariff T2
.report.energy.active.negative.total double kWh Negative active energy (A-) total
.report.energy.active.negative.t1 double kWh Negative active energy (A-) in tariff T1
.report.energy.active.negative.t2 double kWh Negative active energy (A-) in tariff T2
.report.energy.reactive.positive.total double kvarh Positive reactive energy (Q+) total
.report.energy.reactive.positive.t1 double kvarh Positive reactive energy (Q+) in tariff T1
.report.energy.reactive.positive.t2 double kvarh Positive reactive energy (Q+) in tariff T2
.report.energy.reactive.negative.total double kvarh Negative reactive energy (Q-) total
.report.energy.reactive.negative.t1 double kvarh Negative reactive energy (Q-) in tariff T1
.report.energy.reactive.negative.t2 double kvarh Negative reactive energy (Q-) in tariff T2
.report.energy.reactive.imported.inductive.total double kvarh Imported inductive reactive energy in 1st quadrant (Q1) total
.report.energy.reactive.imported.inductive.t1 double kvarh Imported inductive reactive energy in 1st quadrant (Q1) in tariff T1
.report.energy.reactive.imported.inductive.t2 double kvarh Imported inductive reactive energy in 1st quadrant (Q1) in tariff T2
.report.energy.reactive.imported.capacitive.total double kvarh Imported capacitive reactive energy in 2nd quadrant (Q2) total
.report.energy.reactive.imported.capacitive.t1 double kvarh Imported capacitive reactive energy in 2nd quadrant (Q2) in tariff T1
.report.energy.reactive.imported.capacitive.t2 double kvarh Imported capacitive reactive energy in 2nd quadrant (Q2) in tariff T2
.report.energy.reactive.exported.inductive.total double kvarh Exported inductive reactive energy in 3rd quadrant (Q3) total
.report.energy.reactive.exported.inductive.t1 double kvarh Exported inductive reactive energy in 3rd quadrant (Q3) in tariff T1
.report.energy.reactive.exported.inductive.t2 double kvarh Exported inductive reactive energy in 3rd quadrant (Q3) in tariff T2
.report.energy.reactive.exported.capacitive.total double kvarh Exported capacitive reactive energy in 4th quadrant (Q4) total
.report.energy.reactive.exported.capacitive.t1 double kvarh Exported capacitive reactive energy in 4th quadrant (Q4) in tariff T1
.report.energy.reactive.exported.capacitive.t2 double kvarh Exported capacitive reactive energy in 4th quadrant (Q4) in tariff T2
.report.max_demand.active.positive.total double kW Positive active maximum demand (A+) total
.report.max_demand.active.positive.t1 double kW Positive active maximum demand (A+) in tariff T1
.report.max_demand.active.positive.t2 double kW Positive active maximum demand (A+) in tariff T2
.report.max_demand.active.negative.total double kW Negative active maximum demand (A-) total
.report.max_demand.active.negative.t1 double kW Negative active maximum demand (A-) in tariff T1
.report.max_demand.active.negative.t2 double kW Negative active maximum demand (A-) in tariff T2
.report.power_factor double Instantaneous power factor
.report.conv_factor uint Conversion coefficient, the value of the integer by which instantaneous power, energy, current, max demand will be multiplied
.report.volume[].bus uint Bus number for multi-meter installations
.report.volume[].meter_id string Meter identifier for multi-meter installations
.report.volume[].date_time ISO8601 Timestamp (local time) when the volume entry was captured
.report.volume[].cumulative double Cumulative counter reported by the sub-meter on the bus (unit depends on device)
.meter.status string NOT CONNECTED
NO DATA
RECOGNITION
OK
ENCRYPTION KEY
KEY REQUIRED
NOT RECOGNIZED
Meter connection status
.meter.interface string P1
TTL
MBUS
Physical interface
.meter.protocol string DSMR
DLMS
KMP
MEP
Logical interface
.meter.protocol_version string Communication protocol version
.meter.id string Meter identifier (as reported by the device)
.meter.model string Meter model (as reported by the device)
.meter.logical_name string Meter logical name
.meter.vendor string Meter supplier name, if identifiable
.meter.prefix string 3 letter vendor prefixes
.system.id string whatwatt Go unique identifier
.system.date_time ISO8601 Local date time for time zone
.system.date_time_local ISO8601 System timestamp in local time zone with timezone offset
.system.date_time_utc ISO8601 System timestamp in UTC time zone
.system.boot_id string Random string generated after each reboot
.system.time_since_boot double s Time in second since boot

Common Issues & Solutions

Issue: HTTP 401 Unauthorized

  • Symptoms: curl returns "401 Unauthorized" or "Authentication required"
  • Root cause: Device has Web UI password protection enabled
  • Diagnosis: Check device settings - if system.protection: true, authentication is required
  • Solution: Use authentication with device password
  • Code pattern: curl --anyauth -u ":YOUR_PASSWORD" http://device/api/v1/report
  • Related: HTTP Digest Authentication Guide

Issue: Empty or zero values in response

  • Symptoms: Many fields return 0 or null values
  • Root cause: Meter doesn't provide all OBIS objects or communication issue
  • Diagnosis: Check meter.status field - should be "OK"
  • Solution:
  • If meter.status != "OK": Check physical meter connection
  • If status is "OK": Meter model simply doesn't provide those measurements
  • Code pattern: if (data.meter.status === "OK" && data.report.energy.active.positive.total > 0)
  • Related: Different meter models provide different data sets

Issue: Stale data or old timestamps

  • Symptoms: date_time field shows old timestamp (>1 minute ago)
  • Root cause: Meter communication interruption or device time sync issue
  • Diagnosis: Compare report.date_time_utc with current time
  • Solution:
  • Check physical meter connection (MBUS, P1 cable)
  • Verify device time synchronization (NTP)
  • Restart meter communication via device settings
  • Code pattern: time_diff = current_utc - parse_timestamp(data.report.date_time_utc)
  • Related: Meter Communication Settings

Issue: Inconsistent field availability

  • Symptoms: Some API calls include certain fields, others don't
  • Root cause: Different meter types provide different OBIS objects
  • Diagnosis: Check meter.interface and meter.protocol to understand meter type
  • Solution: Use defensive programming - check field existence before accessing
  • Code pattern:
def safe_get_power(data):
    try:
        return data["report"]["instantaneous_power"]["active"]["positive"]["total"]
    except KeyError:
        return None  # Field not available for this meter type
  • Related: OBIS code availability varies by meter manufacturer

Issue: Three-phase vs single-phase confusion

  • Symptoms: Phase L2/L3 values always zero on single-phase meters
  • Root cause: Single-phase meters only provide L1 measurements
  • Diagnosis: Check if voltage.l2 and voltage.l3 are consistently zero
  • Solution: For single-phase systems, use only total and l1 values
  • Code pattern: total_power = data.report.instantaneous_power.active.positive.total
  • Related: Meter installation type determines available phases

Issue: Network connectivity problems

  • Symptoms: Connection timeouts, DNS resolution failures
  • Root cause: Device not reachable on network
  • Diagnosis:
  • Ping device IP address
  • Check mDNS name resolution: ping whatwatt-XXXXXX.local
  • Verify device is on same network segment
  • Solution:
  • Use device discovery tools
  • Check WiFi/Ethernet settings
  • Verify network firewall rules
  • Code pattern: Include proper timeout and retry logic in HTTP clients
  • Related: Device Discovery, Network Setup

Usage Patterns

Pattern: Real-time energy monitoring dashboard

Use case: Display current power consumption and generation Method: Periodic REST API polling Code:

import requests
from requests.auth import HTTPDigestAuth
import time

def get_live_power(device_ip, password=None):
    """Get current power import/export values"""
    auth = HTTPDigestAuth("", password) if password else None

    try:
        response = requests.get(
            f"http://{device_ip}/api/v1/report",
            auth=auth,
            timeout=5
        )
        response.raise_for_status()
        data = response.json()

        if data["meter"]["status"] != "OK":
            return None, f"Meter status: {data['meter']['status']}"

        power_data = {
            "import_kw": data["report"]["instantaneous_power"]["active"]["positive"]["total"],
            "export_kw": data["report"]["instantaneous_power"]["active"]["negative"]["total"],
            "timestamp": data["report"]["date_time_utc"]
        }
        return power_data, None

    except requests.RequestException as e:
        return None, f"Network error: {e}"
    except KeyError as e:
        return None, f"Data format error: {e}"

# Usage example
while True:
    power, error = get_live_power("192.168.1.100", "device_password")
    if power:
        print(f"Import: {power['import_kw']:.3f} kW, Export: {power['export_kw']:.3f} kW")
    else:
        print(f"Error: {error}")
    time.sleep(30)  # Poll every 30 seconds

Expected result: Live power readings every 30 seconds Error handling: Graceful handling of network issues and meter communication problems

Pattern: Energy usage analysis and reporting

Use case: Calculate daily/monthly energy consumption Method: REST API polling with data aggregation Code:

import requests
from datetime import datetime, timedelta
import json

class EnergyMonitor:
    def __init__(self, device_ip, password=None):
        self.device_ip = device_ip
        self.auth = HTTPDigestAuth("", password) if password else None
        self.last_energy = None

    def get_current_energy(self):
        """Get current cumulative energy readings"""
        response = requests.get(
            f"http://{self.device_ip}/api/v1/report",
            auth=self.auth
        )
        data = response.json()

        return {
            "timestamp": datetime.fromisoformat(data["report"]["date_time_utc"].replace("Z", "+00:00")),
            "imported_kwh": data["report"]["energy"]["active"]["positive"]["total"],
            "exported_kwh": data["report"]["energy"]["active"]["negative"]["total"]
        }

    def calculate_period_usage(self, hours=24):
        """Calculate energy usage over specified period"""
        current = self.get_current_energy()

        if self.last_energy is None:
            self.last_energy = current
            return None  # Need baseline measurement

        # Calculate differences
        time_diff = (current["timestamp"] - self.last_energy["timestamp"]).total_seconds() / 3600

        if time_diff >= hours:
            usage = {
                "period_hours": time_diff,
                "imported_kwh": current["imported_kwh"] - self.last_energy["imported_kwh"],
                "exported_kwh": current["exported_kwh"] - self.last_energy["exported_kwh"],
                "net_kwh": (current["imported_kwh"] - self.last_energy["imported_kwh"]) -
                          (current["exported_kwh"] - self.last_energy["exported_kwh"])
            }
            self.last_energy = current
            return usage

        return None  # Not enough time elapsed

# Usage
monitor = EnergyMonitor("192.168.1.100", "password")
usage = monitor.calculate_period_usage(24)  # Daily usage
if usage:
    print(f"Daily usage: {usage['net_kwh']:.2f} kWh net")

Pattern: Solar system monitoring

Use case: Track solar production and self-consumption Method: REST API with solar-specific data extraction Code:

def analyze_solar_system(device_ip, password=None):
    """Analyze solar system performance"""
    auth = HTTPDigestAuth("", password) if password else None

    response = requests.get(f"http://{device_ip}/api/v1/report", auth=auth)
    data = response.json()

    # Current values
    import_power = data["report"]["instantaneous_power"]["active"]["positive"]["total"]
    export_power = data["report"]["instantaneous_power"]["active"]["negative"]["total"]

    # Cumulative values
    total_imported = data["report"]["energy"]["active"]["positive"]["total"]
    total_exported = data["report"]["energy"]["active"]["negative"]["total"]

    # Solar analysis
    solar_analysis = {
        "currently_producing": export_power > 0,
        "current_production_kw": export_power,
        "current_consumption_kw": import_power,
        "current_self_consumption_kw": max(0, import_power - export_power) if export_power > 0 else import_power,
        "lifetime_production_kwh": total_exported,
        "lifetime_consumption_kwh": total_imported,
        "net_meter_reading": total_imported - total_exported
    }

    return solar_analysis

# Usage
solar_data = analyze_solar_system("192.168.1.100")
print(f"Solar producing: {solar_data['currently_producing']}")
print(f"Production: {solar_data['current_production_kw']:.3f} kW")
print(f"Self-consumption: {solar_data['current_self_consumption_kw']:.3f} kW")

Pattern: Three-phase load balancing analysis

Use case: Monitor electrical load distribution across phases Method: REST API with per-phase data analysis Code:

def analyze_phase_balance(device_ip, password=None):
    """Analyze three-phase load distribution"""
    auth = HTTPDigestAuth("", password) if password else None

    response = requests.get(f"http://{device_ip}/api/v1/report", auth=auth)
    data = response.json()

    # Extract per-phase data
    power = data["report"]["instantaneous_power"]["active"]["positive"]
    voltage = data["report"]["voltage"]
    current = data["report"]["current"]

    phases = {
        "L1": {
            "power_kw": power["l1"],
            "voltage_v": voltage["l1"],
            "current_a": current["l1"]
        },
        "L2": {
            "power_kw": power["l2"],
            "voltage_v": voltage["l2"],
            "current_a": current["l2"]
        },
        "L3": {
            "power_kw": power["l3"],
            "voltage_v": voltage["l3"],
            "current_a": current["l3"]
        }
    }

    # Calculate balance metrics
    total_power = power["total"]
    phase_powers = [phases[p]["power_kw"] for p in phases]
    active_phases = [p for p in phase_powers if p > 0]

    if len(active_phases) > 1:
        max_phase = max(phase_powers)
        min_phase = min([p for p in phase_powers if p > 0])
        imbalance_pct = ((max_phase - min_phase) / max_phase) * 100 if max_phase > 0 else 0
    else:
        imbalance_pct = 0

    return {
        "phases": phases,
        "total_power_kw": total_power,
        "active_phases": len(active_phases),
        "imbalance_percent": imbalance_pct,
        "is_balanced": imbalance_pct < 10  # Less than 10% imbalance
    }

# Usage
balance = analyze_phase_balance("192.168.1.100")
print(f"Phase imbalance: {balance['imbalance_percent']:.1f}%")
if not balance["is_balanced"]:
    print("Warning: Significant phase imbalance detected")

Semantic Field Map

Understanding the JSON response structure for RAG and data processing:

Power Measurements Group (Real-time Values)

  • report.instantaneous_power.active.positive.totalsemantic_name: "current_import_power" → meaning: "Instantaneous power consumption from grid" → unit: "kW" → type: "real_time_measurement"
  • report.instantaneous_power.active.negative.totalsemantic_name: "current_export_power" → meaning: "Instantaneous power fed back to grid" → unit: "kW" → type: "real_time_measurement"
  • report.instantaneous_power.reactive.positivesemantic_name: "current_reactive_power_positive" → meaning: "Inductive reactive power consumption" → unit: "kvar" → type: "real_time_measurement"

Energy Counters Group (Cumulative Values)

  • report.energy.active.positive.totalsemantic_name: "total_energy_imported" → meaning: "Cumulative energy consumed from grid since meter installation" → unit: "kWh" → type: "cumulative_counter"
  • report.energy.active.negative.totalsemantic_name: "total_energy_exported" → meaning: "Cumulative energy fed back to grid since meter installation" → unit: "kWh" → type: "cumulative_counter"
  • report.energy.reactive.positive.totalsemantic_name: "total_reactive_energy_positive" → meaning: "Cumulative positive reactive energy" → unit: "kvarh" → **type": "cumulative_counter"

Electrical Parameters Group (Per-Phase Values)

  • report.voltage.l1, .l2, .l3semantic_name: "line_voltages" → meaning: "RMS voltage for each phase" → unit: "V" → type: "real_time_measurement"
  • report.current.l1, .l2, .l3semantic_name: "line_currents" → meaning: "RMS current for each phase" → unit: "A" → type: "real_time_measurement"
  • report.instantaneous_power.active.positive.l1, .l2, .l3semantic_name: "per_phase_power" → meaning: "Power consumption per individual phase" → unit: "kW" → type: "real_time_measurement"

Device Status Group

  • meter.statussemantic_name: "meter_communication_status" → meaning: "Health of communication with energy meter" → unit: "enum" → type: "status_indicator" → values: ["OK", "NO DATA", "RECOGNITION", etc.]
  • meter.interfacesemantic_name: "meter_interface_type" → meaning: "Physical connection method to meter" → unit: "enum" → type: "device_metadata" → values: ["MBUS", "P1", "TTL", "MEP"]
  • meter.protocolsemantic_name: "meter_protocol_type" → meaning: "Communication protocol used" → unit: "enum" → type: "device_metadata" → values: ["DLMS", "DSMR", "KMP", "MEP"]

Temporal Data Group

  • report.date_time_utcsemantic_name: "measurement_timestamp_utc" → meaning: "When meter reading was taken (UTC)" → unit: "ISO-8601" → type: "timestamp"
  • report.idsemantic_name: "report_sequence_number" → meaning: "Sequential reading number since device boot" → unit: "integer" → type: "sequence_metadata"
  • report.intervalsemantic_name: "seconds_since_last_reading" → meaning: "Time elapsed since previous meter reading" → unit: "seconds" → type: "timing_metadata"

System Metadata Group

  • system.idsemantic_name: "device_unique_identifier" → meaning: "Unique hardware identifier of whatwatt Go device" → unit: "hex_string" → type: "device_metadata"
  • system.time_since_bootsemantic_name: "device_uptime_seconds" → meaning: "Seconds since device last restarted" → unit: "seconds" → type: "system_metadata"
  • meter.logical_namesemantic_name: "meter_serial_number" → meaning: "Unique identifier of the energy meter" → unit: "string" → type: "device_metadata"

RAG Processing Patterns:

  • Energy consumption analysis: Compare energy.active.positive.total over time for usage trends
  • Solar production monitoring: Use energy.active.negative.total and instantaneous_power.active.negative.total for solar systems
  • Power quality assessment: Monitor voltage and current values for electrical system health
  • Real-time monitoring: Focus on instantaneous_power fields for live energy flow
  • Data validation: Always check meter.status == "OK" before processing measurements
  • Multi-phase analysis: Use per-phase data (l1, l2, l3) for load balancing insights