Reading Current Scaler Values

Document Context

  • Purpose: API for reading current scaler values applied to DLMS meter registers using OBIS codes for data scaling and unit conversion
  • When to use: Understanding meter data scaling, troubleshooting value discrepancies, verifying COSEM Class 3 object scaling
  • Prerequisites: DLMS meter communication, OBIS code knowledge, understanding of COSEM Class 3 objects and power-of-ten scaling
  • Related to: Custom scalers, Meter communication, data reporting endpoints
  • Validates against: DLMS/COSEM standards, OBIS code specifications, meter scaling behavior in COSEM Class 3

Key Facts

  • Endpoint: /api/v1/meter/scalers/current - Reads current scaling factors for OBIS codes
  • Method: GET - Returns JSON array of OBIS codes with their active scalers
  • Compatibility: DLMS meters only, COSEM Class 3 objects, available since firmware 1.2.15
  • Scaling: Power-of-ten multipliers (-3 to +3 typical range)
  • OBIS format: Shortened C.D.E notation for recognized meter registers

Authentication

When a Web UI password is set, HTTP endpoints require HTTP authentication.

Firmware 1.10.X and later: Uses HTTP Digest authentication - Server challenges with WWW-Authenticate: Digest … (realm is the device hostname) - Algorithm: MD5-sess (device advertises MD5-sess; integrity variant supported) - qop: auth (and optionally auth-int for requests with body integrity) - Nonce and opaque are issued by the device; the client must include cnonce and increment nc - Expired nonce: server may return 401 with WWW-Authenticate: …, stale=true. In that case, retry the same request once using the new server challenge, a new cnonce, and reset nc=00000001.

Firmware before 1.10.X: Uses HTTP Basic authentication - Server challenges with WWW-Authenticate: Basic realm="..." - Credentials are base64-encoded in Authorization: Basic <encoded-credentials>

Recommended approach: Use --anyauth in curl to automatically detect and use the appropriate method:

curl --anyauth -u ":<password>" http://whatwatt-ABCDEF.local/api/v1/system

DLMS Only

Currently, reading current scaler values is only available for meters that exchange data in DLMS format.

COSEM Class 3

Scale factors apply only to COSEM Class 3 objects.

How Scalers Work

The present value is the value that has been determined by the device itself at the detection stage, covered/overridden by a set of scalers selected by the scalers_set (note that the scalers_set does not have to cover all values).

Endpoint Details

This endpoint allows you to read individual scale values for specific register values that the meter transmits. This API uses a shortened convention of logical name/OBIS, which is in the format C.D.E.

Parameter Value
Endpoint /api/v1/meter/scalers/current
Method GET
Response Content Type application/json
Available Since Firmware version 1.2.15

Response Format

The endpoint returns an array of OBIS codes with their current scaler values.

Response Fields

Field Type Description
obis string Shorthand representation of the OBIS notation (C.D.E format). Only OBIS codes recognized by the device and belonging to COSEM class 3 are included
scaler int Currently applied scaling factor expressed as power of ten (10^scaler)

Scaler Value Interpretation

Scaler Value Multiplier Effect Example
-3 0.001 Divide by 1000 1000 → 1.0
-2 0.01 Divide by 100 150 → 1.50
-1 0.1 Divide by 10 25 → 2.5
0 1 No scaling 100 → 100
1 10 Multiply by 10 5 → 50
2 100 Multiply by 100 3 → 300
3 1000 Multiply by 1000 2 → 2000

Example Request

curl -s http://192.168.1.100/api/v1/meter/scalers/current

Example Response

[
  {
    "obis": "1.8.0",
    "scaler": 0
  },
  {
    "obis": "2.8.0",
    "scaler": 0
  },
  {
    "obis": "3.8.0",
    "scaler": 0
  },
  {
    "obis": "4.8.0",
    "scaler": 0
  },
  {
    "obis": "1.7.0",
    "scaler": 0
  },
  {
    "obis": "2.7.0",
    "scaler": 0
  },
  {
    "obis": "32.7.0",
    "scaler": 0
  },
  {
    "obis": "52.7.0",
    "scaler": 0
  },
  {
    "obis": "72.7.0",
    "scaler": 0
  },
  {
    "obis": "31.7.0",
    "scaler": -2
  },
  {
    "obis": "51.7.0",
    "scaler": -2
  },
  {
    "obis": "71.7.0",
    "scaler": -2
  }
]

Common OBIS Codes

Energy Values (typically scaler: 0)

  • 1.8.0 - Positive active energy total
  • 2.8.0 - Negative active energy total
  • 3.8.0 - Positive reactive energy total
  • 4.8.0 - Negative reactive energy total

Power Values (typically scaler: 0)

  • 1.7.0 - Positive active instantaneous power
  • 2.7.0 - Negative active instantaneous power

Voltage Values (typically scaler: 0)

  • 32.7.0 - Voltage L1
  • 52.7.0 - Voltage L2
  • 72.7.0 - Voltage L3

Current Values (typically scaler: -2)

  • 31.7.0 - Current L1 (often scaled by 0.01)
  • 51.7.0 - Current L2 (often scaled by 0.01)
  • 71.7.0 - Current L3 (often scaled by 0.01)

Use this endpoint to understand how raw meter values are being scaled before they appear in the final report data.