Custom Meter Scalers

Document Context

  • Purpose: Custom scaler configuration API for overriding DLMS meter scaling factors using OBIS codes with wildcard support
  • When to use: Normalizing units across different meters, correcting meter scaling issues, standardizing data for analysis
  • Prerequisites: DLMS meter setup, OBIS code understanding, knowledge of COSEM Class 3 objects and meter data units
  • Related to: Current scalers, Meter communication, device settings configuration
  • Validates against: COSEM Class 3 object requirements, OBIS code validation, scaler range limits (-6 to +6)

Key Facts

  • Endpoint: /api/v1/meter/scalers/custom - Configure custom scaling factors for meter data
  • Methods: GET (read), POST (set) - JSON array of OBIS/scaler pairs
  • OBIS format: C.D.E notation with wildcard support (255 for all E values)
  • Scaler range: -6 to +6 power-of-ten multipliers for unit conversion
  • Priority: Custom scalers override device-detected scalers when configured

Authentication

When a Web UI password is set, HTTP endpoints require HTTP authentication.

Firmware 1.10.X and later: Uses HTTP Digest authentication - Server challenges with WWW-Authenticate: Digest … (realm is the device hostname) - Algorithm: MD5-sess (device advertises MD5-sess; integrity variant supported) - qop: auth (and optionally auth-int for requests with body integrity) - Nonce and opaque are issued by the device; the client must include cnonce and increment nc - Expired nonce: server may return 401 with WWW-Authenticate: …, stale=true. In that case, retry the same request once using the new server challenge, a new cnonce, and reset nc=00000001.

Firmware before 1.10.X: Uses HTTP Basic authentication - Server challenges with WWW-Authenticate: Basic realm="..." - Credentials are base64-encoded in Authorization: Basic <encoded-credentials>

Recommended approach: Use --anyauth in curl to automatically detect and use the appropriate method:

curl --anyauth -u ":<password>" http://whatwatt-ABCDEF.local/api/v1/system

DLMS Only

These settings operate exclusively for messages in the DLMS format.

COSEM Class 3

Scale factors apply only to COSEM Class 3 objects.

Alternative Method

Custom scalers can also be configured from the device's WebUI.

Endpoint Details

This endpoint allows for the setting of individual scaling values for specific register values transmitted by the meter. This API uses a shortened convention of logical name/OBIS, which is in the format C.D.E.

Parameter Value
Endpoint /api/v1/meter/scalers/custom
Methods GET, POST
Response Content Type application/json

Configuration Fields

Field Type Range Description
obis string 0..254.0..254.0..255 C.D.E part of the logical OBIS code (e.g., "1.8.0"). Use "255" as wildcard for all E values (e.g., "1.8.255" applies to all tariffs)
scaler int -6..6 Scaler value expressed as power of ten (10^scaler)

OBIS Wildcard Usage

OBIS Pattern Effect Example
1.8.0 Apply to specific register Only positive active energy total
1.8.255 Apply to all E values All positive active energy registers (T0, T1, T2, etc.)
32.7.255 Apply to all voltage phases All voltage measurements

Scaler Value Effects

Scaler Multiplier Use Case Example
-6 0.000001 Micro units µA, µV
-3 0.001 Milli units mA, mV
-2 0.01 Centi units Currency (cents)
-1 0.1 Deci units Decimal precision
0 1 No scaling Default
1 10 Deka units -
2 100 Hecto units -
3 1000 Kilo units kW, kWh
6 1000000 Mega units MW, MWh

Examples

Read Current Custom Scalers

curl -s http://192.168.1.100/api/v1/meter/scalers/custom

Response:

[
  {
    "obis": "1.7.0",
    "scaler": -1
  },
  {
    "obis": "2.7.0",
    "scaler": -1
  }
]

Set Custom Scalers

curl -X POST -H "Content-Type: application/json" \
     -d '[
       {
         "obis": "1.7.0",
         "scaler": -2
       },
       {
         "obis": "1.8.255",
         "scaler": 3
       }
     ]' \
     http://192.168.1.100/api/v1/meter/scalers/custom

Common Configuration Examples

Scale All Energy Values to kWh

[
  {
    "obis": "1.8.255",
    "scaler": 3
  },
  {
    "obis": "2.8.255",
    "scaler": 3
  }
]

Scale All Current Values to Amperes

[
  {
    "obis": "31.7.0",
    "scaler": -2
  },
  {
    "obis": "51.7.0",
    "scaler": -2
  },
  {
    "obis": "71.7.0",
    "scaler": -2
  }
]

Scale Power Values to kW

[
  {
    "obis": "1.7.0",
    "scaler": 3
  },
  {
    "obis": "2.7.0",
    "scaler": 3
  }
]

Practical Use Cases

Unit Conversion

  • Convert Wh to kWh by setting scaler to 3
  • Convert mA to A by setting scaler to -3
  • Convert centivolts to volts by setting scaler to -2

Meter Compatibility

  • Some meters report values in different base units
  • Custom scalers normalize values across different meter types
  • Ensures consistent units in reports and MQTT messages

Data Processing

  • Pre-scale values for specific applications
  • Reduce computation load in client applications
  • Standardize units for data analysis

Important Notes

Validation Required

  • Only OBIS codes belonging to COSEM class 3 should be defined
  • Invalid OBIS codes will be rejected
  • Scaler values outside -6..6 range are not permitted

Best Practice

  • Test scalers with known meter values before production use
  • Document custom scaler configurations for maintenance
  • Use wildcards (255) carefully to avoid unintended scaling

Priority

Custom scalers override device-detected scalers when both are present.